FlowBench / Circulator Pump TDH & Power

Circulator Pump Total Dynamic Head (TDH) & Power Calculator

Sum index-circuit pipe friction, fittings equivalent length, boiler/chiller, terminal coil, and control valve pressure drops to determine pump TDH, Hydraulic HP/kW, Brake Shaft Power, and the parabolic system head curve.

Index Circuit TDH Breakdown WHP / BHP / Wire kW Dynamic System Curve SVG HI 14.3 / ASHRAE
Pump Head & Shaft Power Workbench Live System Curve

Index Circuit & Equipment Drops ID: 1.985 in

GPM
ft
% len
psi
psi
psi
ft H₂O
°F
% vol
%
%

TDH Breakdown & Pump Power 3.63 ft/s

Total Dynamic Head (TDH) 13.45 psi
31.7 ft H₂O
Pipe + Fittings Head22% of TDH
6.92 ft H₂O
Equipment + Valve Head78% of TDH
24.75 ft H₂O
Hydraulic Power (WHP)
0.27 HP
Brake Shaft Power (BHP)Wire: 0.40 kW
0.44 HP
Dynamic pump system head curve plotting head versus flow rate with operating duty point
Pump Selection Diagnostics

Calculating pump TDH and system curve...

Worked Equations & Live Substitution

Total Dynamic Head (TDH) & System Curve
TDH = H_static + h_pipe(1 + %fit) + ΣΔP_equip / (ρg)
Live: ...

Dynamic head varies with flow squared: H(Q) = H_static + k · Q².

Hydraulic & Brake Shaft Power
WHP = (Q · TDH · SG) / 3960  |  BHP = WHP / ηₚ
Live: ...

In SI units: P_hyd(kW) = ρ(kg/m³) · g · Q(m³/s) · TDH(m) / 1000.

ASHRAE & HI Circulator Sizing Guidance

Pump Selection Best Practices

  • Target BEP: Select a circulator whose Best Efficiency Point (BEP) falls within 80%–110% of design flow and TDH.
  • Avoid Excessive Safety Factors: Compounding oversized pipe friction + oversized equipment ΔP pushes pumps far right on the curve or wastes energy across throttled balancing valves.
  • Control Valve Authority: Ensure the control valve drop accounts for 25%–50% of the controlled branch drop for stable modulation.

Efficiency & VFD Turndown

  • Wet-Rotor vs. Base-Mounted: Small ECM wet-rotor circulators typically achieve 40%–60% hydraulic efficiency; larger end-suction centrifugal pumps achieve 65%–82%.
  • Affinity Law Savings: In closed loops (H_static = 0), reducing flow by 20% via a VFD cuts shaft power by ~49% (P ∝ Q³).

Frequently Asked Questions

Why is static elevation head equal to zero in a closed hydronic loop?

In a closed, air-free hydronic loop, the static weight of fluid going up the supply riser is balanced by the equal column of fluid returning down the return riser. Therefore, the circulator pump only overcomes dynamic friction losses in piping, fittings, coils, boilers/chillers, and control valves.

What is the index circuit in hydronic pump TDH sizing?

The index circuit is the hydraulically longest or highest-resistance parallel path from the pump discharge through the equipment and back to the pump suction. Sizing the pump for the index circuit guarantees adequate flow to every parallel branch once balanced.

What is a typical fittings allowance percentage for preliminary TDH calculations?

ASHRAE preliminary sizing commonly adds 30% to 50% of straight pipe length as an equivalent-length allowance for elbows, tees, reducers, and isolation valves in typical mechanical rooms and branch piping.

What is the difference between Hydraulic HP, Brake HP (BHP), and Wire-to-Water kW?

Hydraulic (water) HP is the pure fluid power imparted to the water (Q × TDH × SG / 3960). Brake HP divides hydraulic power by pump hydraulic efficiency to determine shaft load, and Wire-to-Water power further divides by motor/VFD efficiency to determine electrical draw.