Control Valve Cᵥ / Kᵥ Sizing & Valve Authority Calculator

Determine exact required valve flow coefficients (Cᵥ & Kᵥ), evaluate actual pressure drop for a selected nominal valve, and verify Valve Authority N against ASHRAE control stability thresholds.

ISA-75.01 Liquid Sizing Cᵥ ↔ Kᵥ Conversion Valve Authority N Installed Curve SVG
Control Valve Sizing & Authority Workbench ISA-75.01 / ASHRAE

Branch Flow & Valve Selection SG: 0.983

GPM
psi
psi
Cᵥ
°F
% vol

Valve Coefficients & Authority Good / Acceptable

Required Valve Flow Coefficient Required Kᵥ = 6.44
7.44 Cᵥ
Actual Valve ΔP (at Selected Cᵥ)7.9 ft H₂O
3.46 psi
Valve Authority (N)Sel. Kᵥ: 6.92
0.37
Flow at 50% Lift (Installed)
23.6%
Total Branch ΔP
9.46 psi
Inherent vs. installed control valve flow characteristic curve and valve authority stability bar
Control Stability Assessment

Calculating valve sizing and authority...

Worked Equations & Live Substitution

ISA-75.01 Liquid Flow Coefficient (Cᵥ & Kᵥ)
Cᵥ = Q(GPM) · √( SG / ΔP(psi) )  |  Kᵥ = 0.865 · Cᵥ
Live: ...

Actual pressure drop for a selected nominal Cᵥ scales as ΔP_act = SG · (Q / Cᵥ)².

Valve Authority (N) & Installed Distortion
N = ΔP_valve / (ΔP_valve + ΔP_loop)
Live: ...

ASHRAE targets N ≥ 0.25–0.50 for modulating two-way and three-way control valves.

ASHRAE Valve Authority & Trim Guidance

Authority Rating Bands

  • N ≥ 0.50 (Excellent): Installed curve tracks inherent characteristic closely; tight temperature control across 10%–100% load.
  • N = 0.25–0.49 (Good / Acceptable): Standard ASHRAE commercial HVAC target for modulating coil control valves.
  • N < 0.25 (Marginal / Poor): Valve is oversized; consider dropping one nominal valve port size.

Trim & Differential Pressure Tips

  • Equal-Percentage Coils: Compensates for nonlinear coil heat transfer at low flows, giving linear room temperature response.
  • PICV Alternative: Pressure-Independent Control Valves hold internal ΔP constant across the orifice, maintaining effective N ≈ 1.0 even when system pressures swing.

Frequently Asked Questions

What is Valve Authority (N) and why does ASHRAE target N ≥ 0.25 to 0.50?

Valve Authority N = ΔP_valve / (ΔP_valve + ΔP_loop) measures the share of total branch pressure drop taken by the fully open control valve. When N falls below 0.25 (oversized valve), the valve barely throttles until nearly closed, causing hunting, poor temperature control, and rapid actuator wear.

How do you convert between flow coefficients Cᵥ and Kᵥ?

Cᵥ is the US GPM of 60°F water passing through the valve at 1 psi pressure drop, while Kᵥ is the flow in m³/h at 1 bar (100 kPa) pressure drop. They are related by Kᵥ = 0.865 × Cᵥ (or Cᵥ = 1.156 × Kᵥ).

Should I choose Equal-Percentage or Linear valve trim for HVAC coils?

Equal-percentage trim is standard for hydronic heating and cooling coils because coil heat output is nonlinear with water flow; the equal-percentage curve compensates so overall thermal output remains nearly linear with actuator signal, especially at valve authorities between 0.25 and 0.50.

What happens if I select a control valve that is line-sized instead of Cᵥ-sized?

Line-sizing a control valve almost always oversizes its Cᵥ by 2× to 4×, collapsing valve authority below 0.15 and forcing the actuator to modulate in the bottom 10% of its stroke.