Boiler / Heat Exchanger Sizing & LMTD Calculator

Compute counter-flow, parallel-flow, and 1-2 shell-and-tube Log Mean Temperature Difference (LMTD), Bowman-Mueller correction factor F, required UA conductance, and primary/secondary fluid flow rates.

LMTD & F-Factor Solver Required UA (BTU/hr·°F & W/K) Primary / Secondary Glycol TEMA / ASHRAE
Heat Exchanger Thermal Workbench LMTD / ε-NTU

Duty, Temperatures & Fluids ε: 66.7%

BTU/hr
F
°F
°F
°F
°F
% vol
% vol

LMTD, Required UA & Loop Flows Valid Profile

Required Conductance (UA = Q / F·LMTD) NTU: 0.86 | F = 1.00
7,192 BTU/(hr·°F)
Effective ΔTₘ (F · LMTD) LMTD: 34.8 °F
34.8 °F
Terminal ΔT₁ / ΔT₂ Approach: 10 °F
30.0 / 40.0
Primary Hot Flow ΔTₕ: 20.0 °F
25.7 GPM
Secondary Cold Flow ΔTc: 30.0 °F
17.0 GPM
Hot and cold stream temperature profile across normalized heat exchanger length
Thermal Sizing Diagnostics

Calculating LMTD and UA...

Worked Equations & Live Substitution

Log Mean Temperature Difference (LMTD)
LMTD = (ΔT₁ − ΔT₂) / ln(ΔT₁ / ΔT₂)
Live: ...

Counter-flow uses ΔT₁ = Tₕ,in − Tc,out and ΔT₂ = Tₕ,out − Tc,in; parallel-flow pairs inlet-to-inlet and outlet-to-outlet.

Heat Exchanger Rate Equation (UA)
Q = U · A · F · LMTD  ⇒  UA = Q / (F · LMTD)
Live: ...

Match required UA to manufacturer plate or shell-and-tube rating at design fouling allowance.

ASHRAE & TEMA Heat Exchanger Design Guidance

Approach Temperature & Arrangement Selection

  • Brazed / Gasketed Plate HX: True counter-flow (F = 1.0) capable of close 2–5°F (1–3°C) terminal approach temperatures, ideal for snow-melt, heat-recovery, and condensing boiler isolation.
  • 1-2 Shell & Tube HX: Subject to temperature-cross limits; maintain Bowman correction factor F ≥ 0.75 or split into multiple shells in series.

Fouling Factor & Glycol Derating

  • Fouling Allowance: Add 10%–20% excess UA margin above clean calculation for closed hydronic loops, or 25%–35% for open cooling tower / DHW heat exchangers.
  • Glycol Viscosity Effect: Glycol increases boundary-layer film thickness and lowers overall U-value; always rate the exchanger at actual glycol % and coldest operating temperature.

Frequently Asked Questions

Why is counter-flow more effective than parallel-flow in hydronic heat exchangers?

In counter-flow, the heated secondary fluid exits adjacent to the hottest entering primary fluid, allowing the cold outlet temperature to exceed the hot outlet temperature (temperature cross) while maintaining a higher Log Mean Temperature Difference (LMTD) and smaller required UA surface area.

When is the LMTD correction factor F less than 1.0?

Pure counter-flow and pure parallel-flow exchangers (including most brazed-plate and gasketed plate-and-frame units) operate with F = 1.0. Multi-pass shell-and-tube (such as 1-shell, 2-tube pass) and crossflow heat exchangers combine counter- and co-current passes, reducing effective ΔTₘ by F < 1.0.

What minimum LMTD correction factor F is acceptable in TEMA design?

TEMA and ASHRAE guidelines recommend keeping F ≥ 0.75 (ideally ≥ 0.80) for shell-and-tube heat exchangers. Below 0.75, the temperature approach is too tight for a single shell pass; use multiple shells in series or a counter-flow plate heat exchanger.

How does glycol on the primary or secondary side affect heat exchanger flow rates?

Aqueous ethylene or propylene glycol has a lower specific heat capacity than pure water, requiring a higher mass and volumetric flow rate (GPM or L/s) on that loop to transfer the same thermal load at a given ΔT.