FlowBench / Hydronic BTU/hr ↔ GPM (ΔT)

Hydronic BTU/hr ↔ GPM Flow Rate (ΔT Calculator)

Bidirectional hydronic energy equation solver for Flow Rate, Thermal Load, or Loop ΔT with temperature-dependent water, ethylene glycol, and propylene glycol specific-heat and density corrections.

Bidirectional 3-Way Solver True ρ × cₚ Factor (vs. 500 Rule) Ethylene & Propylene Glycol ASHRAE Fundamentals
Hydronic Heat Transfer Workbench Solving Flow Rate

Thermal & Fluid Inputs Factor: 490.2

BTU/hr
GPM
°F
°F
% vol

Thermal & Flow Readouts Water Baseline

Required Loop Flow Rate 2.78 m³/h
12.24 GPM
Thermal Capacity10.00 Tons
120.0 MBH
Fluid Heat Factor-2.0% vs 500
490.2
Mass Flow Rate
5,998 lb/hr
Specific Heat (cₚ)SG: 0.978
1.001 BTU/lb·°F
Hydronic coil energy balance diagram showing supply, return, delta-T, and flow rate
Thermal Diagnostics

Evaluating fluid thermal properties...

Worked Equations & Live Substitution

US Imperial Hydronic Heat Equation
Q(BTU/hr) = 8.021 · ρ(lb/ft³) · cₚ(BTU/lb·°F) · GPM · ΔT(°F)
Live: ...

Reduces to Q ≈ 500 · GPM · ΔT only for pure water near 60°F.

SI Metric Hydronic Heat Equation
Q(kW) = ˙V(L/s) · (ρ/1000)(kg/L) · cₚ(kJ/kg·K) · ΔT(K)
Live: ...

Directly tracks mass flow rate (˙m = ρ · ˙V) and fluid specific heat capacity.

ASHRAE Design ΔT & Glycol Derating Guidance

Typical Design ΔT Ranges (ASHRAE HVAC Systems)

  • Condensing Boilers / High-ΔT Loops: 25°F–40°F (14°C–22°C) ΔT reduces pump energy and lowers return temperature for condensing efficiency.
  • Standard Heating / Fin-Tube Baseboard: 20°F (11.1°C) ΔT.
  • Radiant Floor Loops: 10°F–15°F (5.6°C–8.3°C) ΔT to keep floor surface temperatures uniform.
  • Chilled Water Coils: 10°F–14°F (5.6°C–7.8°C) ΔT (42°F supply / 54°F return).

Glycol Thermal Capacity Correction

  • Propylene Glycol (30%–50%): Specific heat drops to ~0.82–0.91 BTU/lb·°F; even with slightly higher density, volumetric heat capacity falls 8%–16%.
  • Pump Flow Impact: Lower volumetric heat capacity requires higher GPM for the same BTU/hr at fixed ΔT, compounding viscosity head loss.

Frequently Asked Questions

Why isn't the hydronic 500 rule always exact?

The common Q = 500 × GPM × ΔT rule assumes pure water at 60°F (density 62.37 lb/ft³ and specific heat 1.00 BTU/lb·°F). At 180°F heating water, density drops to 60.58 lb/ft³, reducing the factor to about 488. With 40% propylene glycol, lower specific heat reduces the factor further to roughly 445–455, requiring ~10% more GPM.

What ΔT should I use for hydronic heating vs. chilled water coils?

Standard ASHRAE hydronic design uses a 20°F (11.1°C) ΔT for baseboard/boiler heating loops (up to 30–40°F for condensing boilers), 10–15°F (5.6–8.3°C) for radiant floor loops, and 10–14°F (5.6–7.8°C) for chilled water cooling coils.

How do I convert BTU/hr to kW and refrigeration tons?

1 kW equals 3,412.14 BTU/hr, and 1 ton of refrigeration equals 12,000 BTU/hr (3.517 kW). For example, a 120,000 BTU/hr load equals 120 MBH, 10.0 tons, or 35.17 kW.

How does glycol affect hydronic loop flow rate?

Because ethylene and propylene glycol have lower specific heat than pure water, a glycol loop must circulate more volumetric flow (GPM or L/s) to carry the same thermal load at the same ΔT, increasing pump energy consumption.