Pipe Internal Diameters & Absolute Roughness Factors
Verified outside diameter (OD), wall thickness, exact internal diameter (ID), cross-sectional flow area, internal fluid volume, and absolute surface roughness (ε) across 3/8" to 12" (DN 10 to DN 300) piping schedules.
ASME B36.10M & ASTM B88
ASTM F876 PEX SDR 9
ASTM F441 CPVC & D3035 HDPE
Live US ↔ SI Columns
Material Roughness (ε) & Hazen-Williams C Summary
Darcy-Weisbach friction calculations depend on relative roughness (ε/D), whereas Hazen-Williams uses the empirical C-factor. Select any material below to filter the dimensional schedule table.
| Pipe Material & Schedule | Governing Standard | Size Range | Abs. Roughness ε (ft) | Hazen-Williams C | Typical Hydronic / Plumbing Service |
|---|
Nominal Size, Wall Thickness, ID & Cross-Sectional Area
Loading pipe schedule rows...
| Material & Schedule | Nominal | DN | OD (in) | Wall (in) | Exact ID (in) | Area (in²) | Vol (gal/100ft) | Roughness ε (ft) |
|---|
Practical ASHRAE & IPC Piping Engineering Notes
Nominal Pipe Size vs. True Bore (ID)
- CTS vs. IPS Sizing: Copper tube and PEX use Copper Tube Size (CTS) where OD = Nominal + 1/8" (e.g., 1" Copper OD = 1.125"). Steel, CPVC, and HDPE use Iron Pipe Size (IPS) where 1" OD = 1.315", and OD only equals nominal size at 14" and above.
- PEX SDR 9 Penalty: Because CTS PEX maintains the same OD as copper but requires a thick SDR 9 polymer wall, 1" PEX (0.862" ID) has 29% less flow area than 1" Copper L (1.025" ID) and produces ~2.3× higher friction loss at equal GPM.
- HDPE DR 11 Thick Wall: At 4" IPS, HDPE DR 11 has an ID of 3.633" vs. 4.026" for Sch 40 Steel—always verify heat-fusion bead and bore ID in geothermal borefields.
Roughness Aging & Code Selection
- New vs. Aged Carbon Steel: Clean commercial steel starts near ε = 0.00015 ft (0.0457 mm), while open condenser water or untreated steel mains can foul to ε = 0.0005–0.003 ft (C = 100 or lower) over 15–20 years.
- Copper Type K, L & M (IPC/ASHRAE): Type K (heaviest wall) is required for direct underground burial and medical gas; Type L is standard for commercial hydronics and domestic risers; Type M is permitted by IPC for above-ground residential distribution where pressures and water quality allow.
- Related Calculators: Use these dimensions directly in the Pipe Head Loss Calculator, Pipe Sizing & Velocity Matrix, and Expansion Tank Sizing.