FlowBench / Reference Tables / Glycol Correction Tables

Ethylene & Propylene Glycol Thermal & Viscosity Correction Tables

ASHRAE-aligned freeze points, burst protection limits, specific heat, specific gravity, viscosity, volumetric flow correction factors, and Darcy-Weisbach head-loss multipliers across 0%–60% aqueous glycol solutions.

ASHRAE Fundamentals 0%–60% Ethylene & Propylene Glycol GPM & Head-Loss Factors US ↔ SI Live Toggle

Freeze Point & Burst Protection Summary (0%–60% ASHRAE Table)

Freeze point marks initial ice crystal (slush) formation; burst point is the lower temperature where slush expands rigidly enough to damage piping. Properties follow ASHRAE Fundamentals Chapter 31 tables (mass/weight percent, practically within ~1–2% of volume premixes for PG and conservative for EG). Maintain inhibited glycol at ≥ 25–30% to prevent corrosion and biological fouling.

Glycol % (vol) EG Freeze (°F) EG Burst (°F) PG Freeze (°F) PG Burst (°F) EG SG (68°F / 20°C) PG SG (68°F / 20°C) ASHRAE Corrosion & Application Guidance

Thermophysical, GPM Flow & Head-Loss Correction Matrix

Loading glycol matrix...

Head-loss factors evaluated via Darcy-Weisbach on 1-1/2" Copper L at 20 GPM baseline water flow.
Chemistry % Vol Temp (°F) Freeze (°F) SG c_p (BTU/lb·°F) Dyn. Visc (cP) Kin. Visc (×10⁻⁵ ft²/s) Flow Factor Head Mult. (Thermal) State

ASHRAE & IPC Glycol System Design Notes

Flow & Pump Head Derating Mechanics

  • Volumetric Flow Correction Factor: Because glycol lowers specific heat (cp), a system transferring the same BTU/hr (kW) at the same ΔT requires higher flow: Qglycol = Qwater × [(ρw · cp,w) / (ρg · cp,g)].
  • Combined Thermal + Viscosity Head Penalty: Higher required flow (head scales ~Q1.8–2.0) plus cold-temperature viscosity spikes (reducing Reynolds number into transitional or laminar flow) commonly increase pump head by 1.35× to 2.2× in chilled/snow-melt loops.
  • Avoid > 50–60% Mixtures: Above 50% propylene glycol at 32°F (0°C), dynamic viscosity exceeds 14 cP, causing severe coil capacity loss and laminar heat-transfer collapse.

Chemistry Selection & Code Compliance

  • Propylene Glycol (GRAS) vs. Ethylene Glycol: IPC and local plumbing codes mandate non-toxic propylene glycol (typically with double-wall vented heat exchangers or RPZ backflow) wherever potable domestic water is heated. Ethylene glycol offers lower viscosity and better heat transfer for closed industrial or snow-melt loops isolated from potable systems.
  • Minimum 25%–30% Inhibitor Rule: Never dilute inhibited glycol below 25% unless topping up with pure inhibitor—under-inhibited solutions accelerate steel and aluminum corrosion faster than plain water.
  • Interactive Tools: Calculate exact interpolated values for any concentration and temperature in Glycol Properties & Flow Derating or Hydronic BTU/hr ↔ GPM.