FlowBench / Reference Tables / Water Properties vs. Temp

Water Density, Vapor Pressure & Kinematic Viscosity vs. Temperature

Complete thermophysical property reference for pure liquid water from 32°F to 212°F (0°C to 100°C) for pump NPSHa cavitation checks, Darcy-Weisbach Reynolds calculations, and hydronic heat-transfer sizing.

32°F–212°F / 0°C–100°C Tanaka / Vogel / Arden-Buck Instant Temperature Lookup US ↔ SI Live Toggle

Exact Water Temperature Lookup & Property Table

Loading temperature rows...

°F
Density & Specific GravitySG = 0.9832
61.38 lb/ft³
Saturation Vapor Pressure6.75 ft H₂O
2.89 psia
Kinematic Viscosity (ν)μ = 0.463 cP
0.507 ×10⁻⁵ ft²/s
Specific Heat & Hydronic Factor1.000 BTU/lb·°F
492.3 BTU/(hr·GPM·°F)
Temp (°F) Alt (°C) Density (lb/ft³) Wt (lb/gal) SG Vapor P (psia) Vapor Hd (ft H₂O) Dyn. Visc (cP) Kin. Visc (×10⁻⁵ ft²/s) c_p (BTU/lb·°F) Factor (BTU/hr·GPM·°F)

ASHRAE, HI & Hydraulic Engineering Notes

Vapor Pressure & Pump Cavitation (NPSHa)

  • Exponential Vapor Pressure Rise: Between 60°F (0.26 psia) and 180°F (7.51 psia), water vapor pressure rises nearly 30×—consuming 17.8 ft (5.4 m) of atmospheric suction head before pipe friction is even subtracted.
  • Boiling at Atmospheric Pressure: At 212°F (100°C), saturation vapor pressure reaches 14.70 psia (101.3 kPa), leaving zero NPSHa in an open-vented atmospheric tank unless the pump has significant flooded elevation head or loop pressurization.
  • Check Cavitation Margin: Verify open and pressurized closed-loop suction margins using the Static Pressure & NPSHa Calculator.

Viscosity Shift & The "500" Hydronic Factor

  • Why Hot Water Has Lower Friction Loss: Water kinematic viscosity drops from 1.21×10⁻⁵ ft²/s (1.12 cSt) at 60°F to 0.51×10⁻⁵ ft²/s (0.47 cSt) at 140°F—more than doubling the Reynolds number and lowering Darcy-Weisbach friction loss by ~15–20%.
  • Beyond the "500" Rule: The rule-of-thumb Q = BTU/hr ÷ (500 × ΔT) holds accurately near 60°F (Factor = 501). At 200°F (93°C) boiler supply, lower water density drops the factor to ~484 (a 3.3% error unless corrected in Hydronic BTU/hr ↔ GPM).
  • Expansion Volume: Water expands ~4.3% by volume from 40°F to 212°F, driving ASME bladder sizing in Hydronic Expansion Tank Sizing.